Home
About BAC
Products
Service
Markets Served
Careers
Resources
Find a Sales Rep
Contact Us
Products   
 


Closed Circuit Cooling Towers: FXV


Overview · Model Selection · Engineering Data · Layout Data · Sound Data
Specifications · Operation and Maintenance · Rigging and Assembly
Downloads: Brochures · Product Reports · Project Reports · CAD Drawings
Engineering Data for FXV Closed Circuit Cooling Towers

Single Air Inlet Models Dual Air Inlet Models


Single Air Inlet Models

Model Fan
Motor HP
Pump
Motor HP
Shipping
Weight
Heaviest
Section
Operating
Weight
Width Length Height
FXV-421
3 to 10 1.5 5050 2900 7730 8' 5-1/4" 6' 1-1/4" 13' 2-3/4"
FXV-422
5370 3220 8190
FXV-423
5710 3560 8680
FXV-424
6050 3900 9160
FXV-431
5 to 15 2 7160 4240 11230 8' 5-1/4" 9' 1-1/4" 13' 2-3/4"
FXV-432
7650 4730 11930
FXV-433
8140 5220 12630
FXV-434
8680 5760 13380
FXV-441
7.5 to 20 3 8760 5120 14220 8' 5-1/4" 12' 1-1/4" 13' 2-3/4"
FXV-442
9410 5770 15150
FXV-443
10060 6420 16080
FXV-444
10770 7130 17070
FXV-Q440
9410 5770 15150
FXV-Q441
10770 7130 17070
FXV-641
10 to 30 5 10890 6730 18560 11' 10" 12' 1-1/4" 15' 10-3/4
FXV-642
11930 7770 20050
FXV-643
12980 8820 21550
FXV-644
14040 9880 23050
FXV-Q640
11930 7770 20050
FXV-Q641
14040 9880 23050
FXV-661
15 to 45 7.5 15510 9690 27070 11' 10" 18' 1-1/4" 16' 4-1/4"
FXV-662
17070 11250 29290
FXV-663
18670 12850 31570
FXV-664
20280 14460 33810
FXV-Q660
17070 11250 29290
FXV-Q661
20280 14460 33810

Dual Air Inlet Models

Model Fan
Motor HP
Pump
Motor HP
Shipping
Weight
Heaviest
Section
Operating
Weight
Width Length Height
FXV-288-31X
20 to 60 (2) 7.5 28150 8050 46470 24' 1/2" 11' 11" 18' 10-3/8"
FXV-288-41X
30910 9430 50160
FXV-288-1QX
30910 9430 50160
FXV-364-31X
25 to 75 (2) 7.5 32170 9390 54440 26' 3-1/2" 13' 11-1/8" 19' 0-3/8"
FXV-364-41X
35450 11030 58800
FXV-364-1QX
35450 11030 58800

One of the Amsted Industries

| Home | About BAC | Products | Markets Served | Employment |
| Resources | Find a Sales Rep | News | Events | Privacy Policy | Contact Us |