Model Selection for Series V Closed Circuit Cooling Towers
Capacity in U.S. Gallons
per minute of water at the hot water/cold water/wet bulb
temperature (°F) conditions shown.
| Model
|
95/85°F |
102/90°F |
115/90°F |
| 72°F |
78°F |
80°F |
72°F |
78°F |
80°F |
72°F |
78°F |
80°F |
| VF1-009-12G |
27 |
16 |
12 |
32 |
24 |
20 |
17 |
12 |
11 |
| VF1-009-22G |
34 |
20 |
15 |
42 |
30 |
26 |
21 |
15 |
13 |
| VF1-009-32G |
41 |
25 |
18 |
50 |
36 |
31 |
26 |
19 |
16 |
| VF1-009-42G |
46 |
27 |
20 |
56 |
40 |
34 |
28 |
20 |
18 |
| VF1-018-02H |
50 |
28 |
20 |
62 |
43 |
37 |
29 |
21 |
18 |
| VF1-018-12H |
71 |
42 |
31 |
86 |
62 |
53 |
44 |
32 |
27 |
| VF1-018-22J |
97 |
60 |
45 |
116 |
86 |
75 |
62 |
46 |
40 |
| VF1-018-32J |
108 |
67 |
51 |
128 |
96 |
83 |
69 |
52 |
46 |
| VF1-018-42J |
117 |
72 |
55 |
139 |
104 |
90 |
75 |
56 |
49 |
| VF1-027-22H |
115 |
70 |
53 |
138 |
102 |
88 |
73 |
55 |
48 |
| VF1-027-22J |
136 |
84 |
64 |
162 |
121 |
105 |
88 |
66 |
58 |
| VF1-027-32K |
165 |
104 |
80 |
195 |
147 |
128 |
108 |
82 |
72 |
| VF1-027-42K |
176 |
111 |
85 |
209 |
157 |
137 |
115 |
87 |
76 |
| VF1-036-21L |
201 |
123 |
93 |
240 |
178 |
154 |
128 |
95 |
83 |
| VF1-036-31L |
216 |
132 |
100 |
258 |
191 |
166 |
138 |
103 |
90 |
| VF1-036-41L |
231 |
141 |
107 |
276 |
204 |
177 |
147 |
109 |
95 |
| VF1-036-51L |
244 |
147 |
111 |
293 |
215 |
186 |
154 |
113 |
99 |
| VF1-048-21M |
269 |
164 |
124 |
323 |
238 |
206 |
171 |
127 |
110 |
| VF1-048-31N |
319 |
196 |
149 |
381 |
282 |
245 |
204 |
152 |
133 |
| VF1-048-41N |
342 |
209 |
158 |
409 |
302 |
262 |
218 |
162 |
141 |
| VF1-072-21O |
368 |
224 |
170 |
441 |
325 |
282 |
234 |
174 |
151 |
| VF1-072-31O |
397 |
242 |
183 |
476 |
351 |
304 |
253 |
188 |
164 |
| VF1-072-41O |
426 |
259 |
196 |
511 |
376 |
326 |
270 |
200 |
174 |
| VF1-096-31O |
406 |
243 |
182 |
489 |
357 |
308 |
254 |
187 |
162 |
| VF1-096-41P |
492 |
296 |
223 |
591 |
433 |
374 |
309 |
228 |
198 |
| VF1-096-51Q |
570 |
342 |
257 |
686 |
501 |
433 |
357 |
263 |
228 |
| VF1-144N-21Q |
623 |
379 |
287 |
747 |
550 |
477 |
395 |
294 |
256 |
| VF1-144N-31R |
723 |
443 |
336 |
865 |
639 |
555 |
461 |
344 |
300 |
| VF1-144N-41R |
770 |
470 |
356 |
922 |
680 |
590 |
490 |
364 |
317 |
| VF1-144-21Q |
642 |
388 |
292 |
771 |
565 |
489 |
404 |
299 |
260 |
| VF1-144-31Q |
696 |
421 |
317 |
836 |
613 |
531 |
439 |
325 |
283 |
| VF1-144-41R |
805 |
492 |
373 |
963 |
711 |
617 |
513 |
382 |
333 |
| VF1-192-31O |
813 |
487 |
365 |
979 |
714 |
616 |
508 |
374 |
325 |
| VF1-192-41P |
984 |
593 |
446 |
1183 |
866 |
749 |
619 |
457 |
397 |
| VF1-192-51Q |
1140 |
685 |
515 |
1372 |
1002 |
866 |
715 |
527 |
457 |
| VF1-216-21O |
928 |
563 |
425 |
1113 |
818 |
709 |
587 |
435 |
379 |
| VF1-216-31P |
1131 |
692 |
526 |
1352 |
999 |
868 |
722 |
538 |
469 |
| VF1-216-41P |
1201 |
741 |
565 |
1432 |
1063 |
925 |
771 |
577 |
505 |
| VF1-288N-21Q |
1247 |
759 |
574 |
1495 |
1100 |
954 |
791 |
588 |
512 |
| VF1-288N-31R |
1447 |
886 |
672 |
1730 |
1278 |
1110 |
923 |
688 |
600 |
| VF1-288N-41R |
1540 |
940 |
712 |
1844 |
1359 |
1180 |
979 |
728 |
635 |
| VF1-288-21Q |
1284 |
776 |
585 |
1542 |
1130 |
978 |
809 |
599 |
520 |
| VF1-288-31Q |
1394 |
843 |
636 |
1673 |
1227 |
1063 |
879 |
651 |
566 |
| VF1-288-41R |
1616 |
973 |
732 |
1942 |
1421 |
1229 |
1016 |
750 |
651 |
| VF1-432-21O |
1858 |
1127 |
851 |
2229 |
1637 |
1419 |
1176 |
871 |
758 |
| VF1-432-31P |
2264 |
1386 |
1052 |
2706 |
1999 |
1737 |
1444 |
1076 |
939 |
| VF1-432-41P |
2409 |
1470 |
1114 |
2882 |
2125 |
1845 |
1532 |
1140 |
994 |
|
|